    Detailed and simplified models of a terminal unit that combines an UFAD system with a floor cooling

    • Autor
      Atienza-Márquez, Antonio; Fernández-Hernández, Francisco ÁngelAutoridad Universidad de Málaga; Domínguez-Muñoz, FernandoAutoridad Universidad de Málaga; Cejudo-López, José ManuelAutoridad Universidad de Málaga
    • Fecha
      2018
    • Editorial/Editor
      Elsevier
    • Palabras clave
      Edificios - Calefacción y ventilación; Calefacción radiante; Calor - Convección
    • Resumen
      This paper analyses the thermal behaviour of an underfloor air distribution system (UFAD) combined with a floor cooling, focusing on the thermal decay (TD). Two new models were implemented: a detailed model based on the convective heat transfer coefficient inside the plenum, and a simplified model based on the bypass factor. To validate the models we performed three experiments. Both, detailed and simplified models, reproduce well the measured TD. The maximum relative errors between the predicted and measured TD were 8.4% (transient state) and 1.3% (steady state). Although differences were higher at transient regimen, the terminal unit is designed to operate with smooth changes of the boundary conditions. As the error obtained by detailed and simplified models was near identical, the model based on the bypass factor is recommended because of its simplicity. A sensitivity analysis was performed. We evaluated: (1) the TD as a function of the supply air temperature and air flow rate, (2) the cooling capacity of the floor, and (3) the cooling capacity of the ventilation air. The paper concludes with a nomographic design chart that brings together all the features of the terminal unit, allowing a quick selection of the operating parameters.
    • URI
      https://hdl.handle.net/10630/32991
    • DOI
      https://dx.doi.org/10.1016/j.applthermaleng.2017.10.093
    • Compartir
      RefworksMendeley
    Mostrar el registro completo del ítem
    Ficheros
    2018_ATE_129_1079-1091_Preprint.pdf (2.009Mb)
    Colecciones
    • Artículos

    Estadísticas

    REPOSITORIO INSTITUCIONAL UNIVERSIDAD DE MÁLAGA
    REPOSITORIO INSTITUCIONAL UNIVERSIDAD DE MÁLAGA
     

     

    REPOSITORIO INSTITUCIONAL UNIVERSIDAD DE MÁLAGA
    REPOSITORIO INSTITUCIONAL UNIVERSIDAD DE MÁLAGA